Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 06/21/2001 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 06/20/2001 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) BANG PLATE PEX LINES IN TOP PLATE ABOVE LAUNDRY 2) FINISH NAILING STRAPS AT HVAC LINES AND TOP PLATE-1ST FLOOR, 2ND FLOOR AND AT CONDENSATE LINES 3) ADD 2ND STUD ON NORTH (FRONT) SIDE OF 4 GANG BOX TO CARRY BEAM ABOVE 4) FIREBLOCK STUD BAY AT NORTHWEST CORNER-1ST FLOOR 5) SHIM NORTH STUD UNDER STAIR HEADER AND HEADER 6) FINISH NAILING HIP TRUSS BRACKETS MASTER CLOSET AND BEDROOM 7) CONFIRM INTEGRITY OF HVAC LINE 90 DEGREE BEND ABOVE UNIT 8) NEUTRALS NOT SEPERATED IN PANEL |