Permit: T01CM01337

Parcel: 110045760


Addresses:

4642 E VIA AZUFRE


Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T01CM01337

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
11/27/2001 PLUMBING - INTERMEDIATE Approved IVRS - Inspection 0000*
11/23/2001 PLUMBING - INTERMEDIATE Denied IVRS - Inspection 0999*/ 1) 8 PSI ON GAS PRESSURE TEST RUN 10 PSI REQUIRED, PENDING GAS PRESSURE TEST, REST OF PLUMBING OK 2) FIREBLOCKING AT MASTER BEDROOM NOT GOOD
11/21/2001 PLUMBING - INTERMEDIATE Denied IVRS - Inspection 0999*/ 1) PROVIDE 10 PSI MINIMUM GAS TEST 2) A.B. LOOSE THRU-OUT 3) FIRE BLOCKING AT M.B.R.
11/20/2001 PLUMBING - INTERMEDIATE Denied IVRS - Inspection 0999*
11/16/2001 PLUMBING - INTERMEDIATE Denied IVRS - Inspection 0999*/ 1) NO APPROVED PLAN OR PERMIT ON SITE
11/14/2001 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000*
11/13/2001 PLUMBING - INTERMEDIATE Denied IVRS - Inspection 0999*/ 1) NO GAS PRESSURE TEST 2) GAS UNION NOT ALLOWED-USE LEFT AND RIGHT HAND COUPLIING 3) SUPPORT 90 VENT FOR MASTER TUB 5) KITCHEN DUCT RESTRICTED