Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 04/26/2001 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* |
| 04/23/2001 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0245*1. SUPPORT J- BOXES ABOVE COLUM MOUNTED RECEPTS. 2, SUPPORT MC CABLE WITHIN 12' EACH BOX OR TERMINATION, & AT 6' INTERVALS. 334-10 NEC. 3. DO NOT SUPPORT ON CEILING GRID WIRES INTENDED TO SUPPORT GRID SYSTEM. ELECTRICAL CONDUIT, CABLE, BOXES, MUST BE SUPPORTED INDENPENT OF GRID & SUPPORT WIRE TO BE TIE'D OFF BOTH ENDS, ART. 300-14-NEC. 4. NEW CEILING LIGHT FIXTURES DO NOT REFLECT PLAN, OPEN J-BOXES. 5. REMOVE TILES ABOVE COLUMNS TO VIEW MC CABEL RUNS IN THEIR ENTIRE RUN. 6. THERE IS STILL CONUIT & J0BOXES BEING INSTALLED BACK (EAST) AREA? |
| 04/10/2001 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000* SALES AREA S PONY WIRES |
| 04/05/2001 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000* 1) BACK DIMIZING WALL OK |