Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T01CM01322
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/26/2001 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000* | |
04/23/2001 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0245*1. SUPPORT J- BOXES ABOVE COLUM MOUNTED RECEPTS. 2, SUPPORT MC CABLE WITHIN 12' EACH BOX OR TERMINATION, & AT 6' INTERVALS. 334-10 NEC. 3. DO NOT SUPPORT ON CEILING GRID WIRES INTENDED TO SUPPORT GRID SYSTEM. ELECTRICAL CONDUIT, CABLE, BOXES, MUST BE SUPPORTED INDENPENT OF GRID & SUPPORT WIRE TO BE TIE'D OFF BOTH ENDS, ART. 300-14-NEC. 4. NEW CEILING LIGHT FIXTURES DO NOT REFLECT PLAN, OPEN J-BOXES. 5. REMOVE TILES ABOVE COLUMNS TO VIEW MC CABEL RUNS IN THEIR ENTIRE RUN. 6. THERE IS STILL CONUIT & J0BOXES BEING INSTALLED BACK (EAST) AREA? | |
04/10/2001 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* SALES AREA S PONY WIRES | |
04/05/2001 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* 1) BACK DIMIZING WALL OK |