Permit: T01CM01239

Parcel: 116276660

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T01CM01239

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
05/14/2001 FRAMING Approved IVRS - Inspection 0000*
05/09/2001 FRAMING Denied IVRS - Inspection 0999*/ 1) TRAP ARM AT BTA REQUIRES CONTINUOUS SIZE TO TRAP 2) PROVIDE MT OR POST CAP AT PATIO PER PLAN 3) PROVIDE NAIL PROTECTION AT BORED STUDS 4) SECURE WIRING AT PANEL 5) RECESSED LIGHT TO CLOSE TO COMBUSTIBLE 6) FIRE STOP FIRE PLACE AT ? 7) RE-INSPECTION FEE DUE PRIOR TO NEXT INSPECTION
05/08/2001 FRAMING Denied IVRS - Inspection 0999*/ 1) MECH NOT COMPLETE 2) REMOVE CREEN AT DRYER VENT T-TOP 3) SECURE GAS LINE 4) NO WATER PRESSURE 5) PROVIDE APPD STRAPS FOR PLUMBING, PLUMBERS TAPE NOT ALLOWED TO HANG ANY PLUMBING 6) GAS LINE NOT CONNECTED AT FIREPLACE 7) NAIL PROTECTION 8) FIRE STOP COLUMN
04/27/2001 FRAMING Not ready for Inspection NOT READY FOR INSP WORK IN PROGRESS