Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 01/07/2002 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* |
| 12/18/2001 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*NOTES 1.) COLUMNS ALREADY COVERED, CANNOT INSPECT WIRING. 2.) SOUTH RAMADA OK. |
| 12/14/2001 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0245*ROMEX TERMINATION IN BOXES MUST HAVE CLAMP-TYPE CONNECTORS. |