Permit: T01CM01228

Parcel: 13311004C

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T01CM01228

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
03/15/2002 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*NOTE: ROUGH & ABOVE CEILIG WILL HAVE TO REFLECT REVISED DRAWINGS, WHICH SHALL BE CITY APPROVED & ON SITE WHEN FINAL CALLED FOR.
03/08/2002 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0245* 1.) NO COMPLIANCE WITH ITEM #3. 2.) ROMEX TO BE SUPPORTED WITHIN 12" EACH TERMINATION PER 336-18 NEC AND 4 1/2 INTERVALS. UNLESS PER EXEPTION.
02/27/2002 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*1.) INSTALL RINGS OR EXTENTION ON OUTSIDE BOXES TO REACH SURFACE. 2.) ID PANEL FEEDERS. 3.) PANEL B TO HAVE INDIVIDUAL CLAMPS FOR BRANCH CIRCUITS. 4.) NO PNL BON APPROVED PLAN. PLANS ON SITE HAVE TO HAVE APPROVED CHANGES. 5. CHANGES ON LIGHTING TO BE REFLECTED INCLUDING EXIT LIGHTS, EM LIGHTS 6.) DIMMER BOXES TO BE SEALED.
01/23/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*OK PARTIAL FOR LIGHTING BELOW AND ABOVE TOWER AREA ONLY.