Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 09/14/2001 |
MECHANICAL - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000*OK FOR SHEET ROCK. |
| 09/12/2001 |
MECHANICAL - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*CONDENSATE DRAINS IN TYPE 4 UNITS NOT SLOPED CORRECTLY. |
| 09/11/2001 |
MECHANICAL - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*CONDENSATE DRAIN NOT SLOPED ADEQUATELY 1ST FLOOR UNITS #4. RECALL FOR INSPECTIONS. |
| 08/16/2001 |
MECHANICAL - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*INSPECTION ON PRE-ROCK EXHAUST DUCTS OK FOR SHEET ROCK. |