Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 04/03/2002 |
PLUMBING - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 03/27/2002 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) H.C. WATER CLOSET HANDLES MUST BE ON OPEN SIDE OF RM (ADA SPEC) 2.) WILL NOT HAVE TO MOVE LAV COUNTER TOPS DUET O PROVISION IN HOAAG MANUAL ALLOWING DIANGLE ACCESIBILITY AS PER STEVE LONG CONVERSATION ON 3-27-02. |
| 03/25/2002 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) CALL IN ALL REQUIRED INSPECTIONS BEFORE FINAL INSPECTION 2.) EXTERIOR CLEANOUTS NOT CUT TO GRADE, NEED APPROVED CLEAN-OUT W/PLUG. 3.) ALL CONDENSATE, AND T & P RELIEF DRAINS NEED 90 ELL OUTSIDE 4.) REVIEW PAGE U6 UNIT TWO BATH ELEVATIONS FOR ADA I ALSO QUESTION THE ALLOWANCE OF 15" FROM CENTER TO EDGE OF COUNTER TOP ON UNIT ONE BATH ELEVATIONS. REVIEW ADA REQUIREMENTS. |