Inspection Status: Denied
Inspection History: PLUMBING - PROGRESS
| Date |
Description |
Inspector |
Results |
Comments |
| 04/15/2002 |
PLUMBING - PROGRESS |
|
Denied |
IVRS - Inspection 0999*1.) SEE NOTES #1 AS REQUESTED 2.) DO NOT COVER. |
| 04/15/2002 |
PLUMBING - PROGRESS |
|
Approved |
IVRS - Inspection 0000*1 |
| 04/03/2002 |
PLUMBING - PROGRESS |
|
Denied |
IVRS - Inspection 0999*1.) WATER SERVICE HAS A LEAK @ BACKFLOW PREVENTER @ MALE ADPT. 2.) MUST HAVE 12"MIN OF COVER ON HORIZONTAL. RUN OUT OF METER SIDE. |
| 03/29/2002 |
PLUMBING - PROGRESS |
|
Denied |
1.) MUST EXPOSE ALL FITTINGS UNDER GROUND @ BACKFLOW PREVENTER PRIOR TO INSPECTION. 2.) SEC SECTION: 609.5 INSTALLATION STANDARDS 94 UPC. |
| 07/09/2001 |
PLUMBING - PROGRESS |
|
Partial Approval |
IVRS - Inspection 0000*1.) AIR PRESSURE TEST 60IBS FOR WATER SERVICE IS OK 2.) WASTE VENT WRAP OK |
| 06/22/2001 |
PLUMBING - PROGRESS |
|
Not ready for Inspection |
IVRS - Inspection 0000*1.) NOT READY FOR INSPECTION |
| 06/19/2001 |
PLUMBING - PROGRESS |
|
Not ready for Inspection |
IVRS - Inspection 0000*1.)NOT READY FOR INSPECTION.2.)MUST PAY REINSPECTION FEE BEFORE.3.)BE READY. |