Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 10/18/2001 |
MECHANICAL - ABOVE CEILING |
|
Approved |
IVRS - Inspection 0000*OK FOR SHEETROCK. |
| 10/16/2001 |
MECHANICAL - ABOVE CEILING |
|
Denied |
IVRS - Inspection 0999*1.) REMOVE EXPOSED PVC IN RETURN AIR PLENUM 2.) PROVIDE FIRE STOP WHERE CONDENSATE DRAINS PENETRATE COMMON WALL. 3.) REPAIR TORN INSULATION ON REFER LINE 2ND FLOOR. |