Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T01CM01210
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/21/2001 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000* | |
| 12/18/2001 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0245*NOTES 1.) SEE LAST INSPECTION WRITE UP 2.) CHECK RECEPT SPACING ALL UNITS 3.) CANNOT INSPECT WALLS WITH DRYWALL STACKED ON BOTH SIDES | |
| 11/19/2001 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0999*1.) BOTTOM UNITS NORTH SIDE INSTALL FLEX CONDUITS TO WH'S & NAIL TO WALL 2.) BOTTOM EAST UNIT STAPLE ROMEX AND ISNTALL INTO BOX AT BATHROOM. 3.) MIDDLE UNITS BOTTOM SUPPORT ROMEX WITHIN 12" OF PANCAKE BOXES 4.) NAIL ALL WH FLEXS TO STUDS 5.) ALL OUTSIDE STORAGE ROOMS SUPPORT ROMEX WITH IN 12" OF BOXES 6.) BOTTOM FLOORS CHECK ALL THE CONNECTS GOING INTO PANELS MUST BE SNAPPED IN. 7.) ALL RANGE CABLES TO BE NAILED WITH IN 12" OFF BOXS HAVE ELECT CONTRACTOR CHECK ALL THIS ITEMS AND RECALL. |