Permit: T01CM01206

Parcel: 13311004C

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T01CM01206

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
09/06/2001 FRAMING Approved IVRS - Inspection 0000*
08/28/2001 FRAMING Partial Approval IVRS - Inspection 0000*
08/27/2001 FRAMING Not ready for Inspection IVRS - Inspection 0000*NOT READY. 1.) REPLACE OVER DRILLED STUD @ KITCHEN SINK VENT, 1ST FLOOR, N.W. APT. 2.) REPLACE SHEAR BLOCKS THROUGHOUT BLDG. 3.) PROVIDE DRAFT STOP @ TOP OF CHASE BEHIND BATHS LINEN CLOSETS 4.) BRACE OR REPLACE OVER NOTCHED STUD @ PLUMBING IN BATHROOM OF 1ST FLOOR NORTH EAST APT. AND BUILD SOFFIT? BRACE NOTED SHEAR PANEL. 5.) PUDDLE WELD NUTS ON "HOLD DOWNS" THAT DON'T FULLY ENGAGE BOLTS 6.) COMPLETE SOFFITS, CHECK NUTS & WSHRS ON ANCHOR BOLTS. 7.) RENAIL LOOSE STUDS, STRAIGHTEN BOWED STUDS, RENAIL LOOSE TOP PLATES 8.) FIX SHINERS @ SHEAR PANELS TO FLOOR TRUSSES 9.) RED HEAD BOTTOM PLATES THAT MISSED THE ANCHOR BOLTS 10.) COMPLETE THE R.C. CHANNEL 11.) DRAFT STOP DOUBLE WALLS EACH 10' 12.) FIRE BLOCK TOP OF DOUBLE WALLS (AT PLATE LINE)
08/23/2001 FRAMING Not ready for Inspection IVRS - Inspection 0000*BLD #7