Permit: T01CM01202

Parcel: 13311004C

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T01CM01202

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
08/24/2001 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
08/13/2001 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0245*1.) INSTALL BUSHED ENDS ON FLEX METAL CONDUIT USED FOR SLEEVES OVER ROMEX 300-15C NEC. 300-16. 2.) INSTALL LISTED CONNECTORS FOR CABLE TERMINIATIONS IN SUB PANELS 370-17 NEC. 3.) CHECK FOR NAIL DAMAGE AT SHEAR WALLS 110-12 NEC.