Permit: T01CM01182

Parcel: 10605093A

Inspection Status: Approved

Inspection History: ELECTRIC - TEMPORARY SERVICE

Date Description Inspector Results Comments
08/16/2001 ELECTRIC - TEMPORARY SERVICE Approved
06/22/2001 ELECTRIC - TEMPORARY SERVICE Denied IVRS - Inspection 0999*1.) NEED BONDING DEVICE 2.) CAN NOT STACK LUGS USE FULL SURFACE AREA 3.) NEED REJECTION CUPS 4.) VERIFY TEMP POWER BOND 5.) NEED APPROVED REVISED ONE LING DIAGRAM
06/20/2001 ELECTRIC - TEMPORARY SERVICE Cancelled IVRS - Ri canceled