Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 06/05/2001 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 06/04/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*CHASE NIPPLE IN TRANSFER CABINATE NOT APPROVED.USE CLOSE NIPPLE WITH LOCKNUTS, BUSHING.250 NEC.INSTALL INSULATED BUSHINGS FEEDER J-BOXES #4 OR LAGER N.E.C.300-4. |
| 05/31/2001 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*1)INSTALL BOND BUSHING ON RISER CONDUIT, 250-94 N.E.C.2)COMPLETE FEEDER WIRING. |