Inspection Status: Approved
Inspection History: ELECTRIC - TEMPORARY POLE
| Date |
Description |
Inspector |
Results |
Comments |
| 06/28/2001 |
ELECTRIC - TEMPORARY POLE |
|
Approved |
|
| 06/27/2001 |
ELECTRIC - TEMPORARY POLE |
|
Partial Approval |
1.)NEED REJECTION CLIPS AT SERVICE DISCONNECT 2.) NEED PANEL SCHEDULE 3.) NEED DISCONNECTING MEANS FOR INSTALL HOT BREAK RM. 4.) NEED WORKING CLEARENCE INFRONT OF SMALL SINK INSTALL HOT DISCONNECT. |
| 06/19/2001 |
ELECTRIC - TEMPORARY POLE |
|
Denied |
IVRS - Inspection 0999* |
| 06/18/2001 |
ELECTRIC - TEMPORARY POLE |
|
Denied |
IVRS - Inspection 0999*NO TEMPORARY POWER WILL BE ISSUED AS PER STEVE LONG INSPECTIONS MANGER. |