Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 06/22/2001 |
ELECTRIC - ABOVE CEILING |
|
Approved |
IVRS - Inspection 0000*OK TO TILE |
| 06/21/2001 |
ELECTRIC - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*1.) FINISH GRID AT FRONT ENTRY FOR EXIT LIGHT |
| 06/20/2001 |
ELECTRIC - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000* 1) finish grid and install exit light at front entry. 2) support m/c cable within 12'' of boxes and fixtures |
| 06/19/2001 |
ELECTRIC - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*1)ATTACH EMERGENCY LIGHT TO GRID AND USE SUPPORT WIRE.2)ATTACH M/C CABLE WITHIN 12" OF JUNCTION BOXES.3)CAN NOT ATTACH M/C CABLE TO GRID.4)FINISH J-BOX MAKE-UP.5)FILL ALL UNUSED OPENINGS IN J-BOXES.6)PLANS DO NOT REFLECT WORK DONE FOR SERVICE-OK 2X4 LAYING. |
| 06/18/2001 |
ELECTRIC - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*OK RM# 207-211 NO |