Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T01CM01129
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/21/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*OK FINAL | |
06/20/2001 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*1)NEED TO SEE FRONT CASH WRAP CONNECTIONS. | |
06/14/2001 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*1)SUPPORT DATA CABLES AS PER CODE-CANNOT LAY ON GRID.2)NEED SUPPORT WIRE TO SUPPORT TRAC.3)SUPPORT CONDUIT WITH IN 3' OF PANELS.4)NEED TO SEE WORK FOR FRONT COUNTER. |
|
06/12/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0920*LOCKED NO ACCESS 2:40 P.M. | |
06/09/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*1)STRAP CONDUIT AS PER CODE-WITHIN 3' OF ENCLOSURE.2)LOOSE FITTINGS AT GUTTER.3)BOND GUTTER.4)NEED BONDING DEVICE ON FLEX.5)USE NEUTRAL SIZED ACCORDING TO 250-66-TABLE.6)GFI RECEPTICAL WIRED IN CORRECT.7)FINISH LAST INSPECTION FOR ABOVE CEILING NO WORK PROGRESS.8)SUPPORT CONDUIT PW/CLIPS.10)CLEAN SURFACES UNDER GROUND LUGS. |
|
06/04/2001 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000* | |
05/25/2001 | ELECTRIC - FINAL | Partial Approval | OK TERM CAN, CTCAN, METER SOCKET 3" CONDUITS AND WIRE UP TO GUTTER. |