Inspection History: ELECTRIC - FINAL

Permit Number - T01CM01129

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/21/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*OK FINAL
06/20/2001 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*1)NEED TO SEE FRONT CASH WRAP CONNECTIONS.
06/14/2001 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*1)SUPPORT DATA CABLES AS PER CODE-CANNOT LAY ON GRID.2)NEED SUPPORT WIRE TO SUPPORT TRAC.3)SUPPORT CONDUIT WITH
IN 3' OF PANELS.4)NEED TO SEE WORK FOR FRONT COUNTER.
06/12/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0920*LOCKED NO ACCESS 2:40 P.M.
06/09/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999*1)STRAP CONDUIT AS PER CODE-WITHIN 3' OF ENCLOSURE.2)LOOSE FITTINGS AT GUTTER.3)BOND GUTTER.4)NEED BONDING DEVICE ON FLEX.5)USE NEUTRAL SIZED ACCORDING
TO 250-66-TABLE.6)GFI RECEPTICAL WIRED IN CORRECT.7)FINISH LAST INSPECTION FOR ABOVE CEILING NO WORK PROGRESS.8)SUPPORT CONDUIT PW/CLIPS.10)CLEAN SURFACES UNDER GROUND LUGS.
06/04/2001 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*
05/25/2001 ELECTRIC - FINAL Partial Approval OK TERM CAN, CTCAN, METER SOCKET 3" CONDUITS AND WIRE UP TO GUTTER.