Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/04/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
| 06/02/2001 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*1)BOND JUNCTION BOX ENCLOSURERS. | |
| 05/30/2001 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*1)LOOSE FITTINGS.2)SUPPORT CONDUIT WITH IN 3' OF FITTINGS AND BOX.3)BOND JUNCTION ENCLOUSER.*NEED TO SEE APPEAL/PAPERWORK. |
|
| 05/22/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*1)A/C DICONNECT CLEARANCE IN VIOLATION OF 110-26 NEC 99.2)PLEASE MARK EACH DISCONNECT W/PERMANENT TAGS.3)K.O.'S MIISSING IN DISCONNECT.4)OLD PANEL BOARD IN VID. OF 110-26. |