Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 03/14/2001 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* |
| 03/13/2001 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999* |
| 03/09/2001 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*/1. ELECTRIC OUTLET MISSING ON WEST WALL. NO AREA ALONG WALL AT FLOOR MAY BE MORE THAN 6 FEET FROM AN OUTELT. 2. ELECTRIC OUTLET REQUIRED ON EAST WALL. BETWEEN 6 FOOT AND 3 FOOT DOORS. 3. #12 WIRE MAX ALLOWED OVER CURRENT DEVICE 20 AMP 30 AMP INSTALLED. 4. BATTERY OPERATED SMOKE DETECTORS REQUIRED IN EACH EXISTING BEDROOM. |