Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date |
Description |
Inspector |
Results |
Comments |
| 04/16/2001 |
EXT METAL CLIPS/EXT SHEATHING |
|
Approved |
IVRS - Inspection 0000* |
| 04/12/2001 |
EXT METAL CLIPS/EXT SHEATHING |
|
Denied |
IVRS - Inspection 0999*/PROVIDE POST UNDER HEADER AT ENTRY OR BUILT UP MEMBER AS PER PLAN, PROVIDE DETAIL 6/SD1 AT BOTTOM OF COLUMN, MISSING SHEAR PANELS AT SLIDER TWO SIDES, HOLDOWN AT BACK NOT INSTALLED AS PER MANF. INSTALLATION STANDARDS, FHA STRAP/PROTECT PLUMBING AT SOLE PLATES, PROVIDE COT/ENGINEERED APPROVED TRUSS CALC'S, PROVIDE DETAIL 13/SD2 NAIL BLOCKS 8DS 6" OC, NOTE: CONTRACTOR HAS BEEN ADVISED NUMEROUS TIMES TO PROVIDE POST AS PER PLAN, A RE INSP FEE WILL BE IMPOSED ON ALL INSPECTIONS CALLED IN FOR WITH SAME RESULT |