Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T01CM01038
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/30/2002 | BUILDING - FINAL | Approved | IVRS - Inspection 0000* | |
04/29/2002 | BUILDING - FINAL | Denied | IVRS - Inspection 0999*/ 1) WATER HEATER "B" VENT MUST TERMINATE 2 FEET HIGHER THAN ANY VERTICAL WALL WITHIN 10 FEET UPC 517.3 2) PROVIDE LADDER ACCESS TO FLOOR ROOF 3) BACK WATER VALVE MUST BE ACCESSIBLE. PROVIDE MANHOLE 4) FURNACE "B" VENT BROKEN-LOOSE IN WALL 5) SHORT CIRCUIT IN GARAGE GFCI CIRCUIT 6) DISPOSAL/DISHWASHER OUTLET NOT ACCESSIBLE 7) STAIRS EXCEED 3/8" DIFFERENCE IN STAIR RISERS 8) MINIMUM ALLOWED RUN IN STAIR 11" PRESENTLY 10" 10) HAND RAIL REQUIRED AT 2 STEP MASTER BEDROOM. STEP RUN ONLY 9" 11) 2ND FLOOR FURNACE LOWER COMBUSTION AIR ONLY 30 SQUARE INCHES. BLOCKED BY SHEET METAL FLANGE | |
04/11/2002 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection 0000$/ 1) DOOR LOCKED 2) FROM OUTSIDE WITHOUT PLANS, NEED ADDRESS NUMBERS, FLUE TO CLOSE TO WINDOW, NEED FRONT ENTRY LANDING |