Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 06/18/2001 |
BUILDING - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 06/15/2001 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) NEUTRAL WIRES ARE NOT PERMITTED TO BE PAIRED UNDER A SINGLE LUG SCREW 2) OCCUPANCY SEPERATION DOOR MUST SELF CLOSE AND LATCH 3) PLUG KNOCKOUT HOLE AT BOTTOM OF ELECTRIC PANEL 4) REPAIR DRYWALL AROUND OUTLET IN KITCHEN |