Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T01CM01008
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/12/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
10/11/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245*NOTES 1.) INSTALL BREAKER BLANKS MECH YARD PANEL 2.) COMPLETE WIRING ALTERATIONS FOR SUMP PUMPS IN FC UNIT SETS. | |
10/08/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245*NOTES 1.) COMPLETE LABELING OF MCC AND MAIN SERVICE SECTION 2.) NEED REVISION FROM ARCH FOR ADDITION OF COND. PUMPS AT FC UNITS. | |
10/05/2001 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000*FIRE ALARM SYSTEM NOT READY. | |
10/01/2001 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000*1.) NOTES 1.) COMPLETE FIXTURE WIRING 2.) LABEL DISCONNECTS, PANELS. | |
08/03/2001 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*DO NOT ENERGIZE POWER IN MECHANICAL YARD TILL APPROVAL FROM APPROPIATE INSPECTIONS ON SIGN OFF SHEET FOR TEMP. POWER. | |
07/30/2001 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*OK TO CLEAR NEW SWITCH GEAR OK TO POWER EXISTING GEAR. |