Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
| Date |
Description |
Inspector |
Results |
Comments |
| 02/01/2002 |
ELECTRIC - UNDERGROUND |
|
Approved |
IVRS - Inspection 0000* |
| 07/23/2001 |
ELECTRIC - UNDERGROUND |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) UNDERGROUND TO SERVICE-OK |
| 07/16/2001 |
ELECTRIC - UNDERGROUND |
|
Denied |
IVRS - Inspection 0999*/ 1) SERVICE RISER LOOSE AT SERVICE PANEL 2) BONDING BUSHING IS LOOSE ON SERVICE RISER 3) BONDING BUSHING CONDUCTOR MUST BE MINIMUM #4 COPPER 4) GROUND RODS MUST BE A MINIMUM OF 6' APART IS PRESENTLY 5' APART |
| 07/06/2001 |
ELECTRIC - UNDERGROUND |
|
Denied |
IVRS - Inspection 0999*/ 1) PROVIDE 24" TRENCH 2) SEE NOTES FROM PRIOR INSPECTION |