Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T01CM01003
Inspection Description - FRAMING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/07/2002 | FRAMING | Approved | IVRS - Inspection 0000* | |
| 05/23/2002 | FRAMING | Partial Approval | IVRS - Inspection 0000* | |
| 05/14/2002 | FRAMING | Denied | IVRS - Inspection 0999* | |
| 04/30/2002 | FRAMING | Not ready for Inspection | IVRS - Inspection 0000*/ 1) SPLIT IN PLATES TO OCCURE AT STUDS 2) HEADERS IN CORRECTLY INSTALLED OR MISSING 3) WRONG NAILS USED EXTERIOR PLYWOOD 4) DOUBLE JOIST HANGERS INCORRECTLY IN ADEQUATELY INSTALLED 5) TO LARGE OF GAP IN PLYWOOD ROOFING 6) INSTALL H2.5'S RAFTERS TO BEARING 7) GROUND ALL METAL ELECTRICAL BOXES 8) INSTALL ROMEX CONNECTIONS METAL ELECTRIC BOXES 9) ELECTRIC INT PER PLAN 10) ALSO REVISE AS TO RELOCATE AND OR CHANGE AC/HEAT 11) CHECK CAN LIGHTS CLEARANCE TO PLYWOOD 12) EXTERIOR PLYWOOD JOINTS TO OCCUR 13) AC/HEAT TO BE ON SEPERATE CIRCUIT OVER STUDS OR BLOCKING 14) STOPPED INSPECTION 15) CORRECT ALL ITEMS 16) RECALL WHEN READY |