Permit: T01CM01003

Parcel: 133367880


Addresses:

428 N SCHRADER LN


Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T01CM01003

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
06/07/2002 FRAMING Approved IVRS - Inspection 0000*
05/23/2002 FRAMING Partial Approval IVRS - Inspection 0000*
05/14/2002 FRAMING Denied IVRS - Inspection 0999*
04/30/2002 FRAMING Not ready for Inspection IVRS - Inspection 0000*/ 1) SPLIT IN PLATES TO OCCURE AT STUDS 2) HEADERS IN CORRECTLY INSTALLED OR MISSING 3) WRONG NAILS USED EXTERIOR PLYWOOD 4) DOUBLE JOIST HANGERS INCORRECTLY IN ADEQUATELY INSTALLED 5) TO LARGE OF GAP IN PLYWOOD ROOFING 6) INSTALL H2.5'S RAFTERS TO BEARING 7) GROUND ALL METAL ELECTRICAL BOXES 8) INSTALL ROMEX CONNECTIONS METAL ELECTRIC BOXES 9) ELECTRIC INT PER PLAN 10) ALSO REVISE AS TO RELOCATE AND OR CHANGE AC/HEAT 11) CHECK CAN LIGHTS CLEARANCE TO PLYWOOD 12) EXTERIOR PLYWOOD JOINTS TO OCCUR 13) AC/HEAT TO BE ON SEPERATE CIRCUIT OVER STUDS OR BLOCKING 14) STOPPED INSPECTION 15) CORRECT ALL ITEMS 16) RECALL WHEN READY