Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
Permit Number - T01CM01003
Inspection Description - EXT METAL CLIPS/EXT SHEATHING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/07/2002 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection 0000* | |
| 05/23/2002 | EXT METAL CLIPS/EXT SHEATHING | Partial Approval | IVRS - Inspection 0000*/ 1) GROUND ALL METAL ELECTRIC BOXES 2) NEW RAFTERS AT EXISTING OVERLAP INSTALL SOLID BEARING WOOD BETWEEN NEW RAFTER AND TOP OF DOUBLE TOP PLATE OF NEW WALL 3) EXTERIOR WOOD SHEATHING REQUIRES BLOCKING AND NAILING ALL JOINTS 4) RENAIL ALL LOOSE EXTERIOR PLYWOOD; WEST PARAPET WALL OUT OF PLAN 5) INSTALL POST TO BEAM CONNECTION BOTH SIDES PORCH POST | |
| 05/14/2002 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection 0999*/ 1) RENAIL SHEATHING AT TOP OF WEST WINDOW NORTH END 2) REPLACE HEADER OF DOOR INTO EXISTING HOUSE 3) PROVIDE ADEQUATE HEADER FOR EAST WINDOW AND WEST WINDOW 4) PROVIDE INFORMATION REGARDING TYPE, SIZE AND LOCATION OF HEAT/AC UNIT 5) PLANS CALL FOR 2 X 8 BOX HEADERS |