Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T01CM00980
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/15/2002 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection 0000*OK 3RD FLOOR. | |
01/11/2002 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection 0000* | |
01/09/2002 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection 0245*NOTES 1.) BEND OUT SIEZMIC CLIPS FOR 2 X 4 LAY IN FIXTURES. 2.) WHERE CEILING WIRES ARE USED AS SUPPORT, FOR CONDUIT IT, MUST BE INDEPENDANT OF WIRES USED TO SUPPORT GRID SYSTEM AND TIED OF AT BOTH ENDS. 3.) EMERGENCY BRANCH CIRCUITS MUST INSTALLED USING NOW FLEXABLE CONDUIT. PER ART 517 N.E.C. | |
07/30/2001 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*OK 364 THRU 376 |