Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 03/21/2002 |
MECHANICAL - ABOVE CEILING |
|
Approved |
IVRS - Inspection 0000*MECH FINAL ABOVE CEILING APPROVED. |
| 03/18/2002 |
MECHANICAL - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*NOT CLEARED TO COVER GRID |
| 02/27/2002 |
MECHANICAL - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*1.) PROVIDE LISTING ON FIRE DAMPERS IN 4HR. WALL 2.) WILL CHECK ACCESS DOORS NEXT VISIT. 3.) PROVIDE SECONDARY CONDENSATE DRAIN SEPERATE FROM PRIMARY ON AIR HANDLER. DO NOT BLOCK ACCESS FOR SERVICE. 4.) OK FOR ANGLES ON FIRE DAMPERS. |
| 11/01/2001 |
MECHANICAL - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*FIRE STOP AROUND FIRE DAMPER ANGLE IRON FRAMES. |
| 10/25/2001 |
MECHANICAL - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*STILL NEED TO SEE FIRE DAMPERS ON EXHAUST SYSTEM, OFFICES NORTH END OF PHASE I. OK FOR PARTIAL CEILING TILES. |