Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T01CM00979

Parcel: 13314227B


Addresses:

1400 N WILMOT RD


Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T01CM00979

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
03/21/2002 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection 0000*MECH FINAL ABOVE CEILING APPROVED.
03/18/2002 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000*NOT CLEARED TO COVER GRID
02/27/2002 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000*1.) PROVIDE LISTING ON FIRE DAMPERS IN 4HR. WALL 2.) WILL CHECK ACCESS DOORS NEXT VISIT. 3.) PROVIDE SECONDARY CONDENSATE DRAIN SEPERATE FROM PRIMARY ON AIR HANDLER. DO NOT BLOCK ACCESS FOR SERVICE. 4.) OK FOR ANGLES ON FIRE DAMPERS.
11/01/2001 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000*FIRE STOP AROUND FIRE DAMPER ANGLE IRON FRAMES.
10/25/2001 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000*STILL NEED TO SEE FIRE DAMPERS ON EXHAUST SYSTEM, OFFICES NORTH END OF PHASE I. OK FOR PARTIAL CEILING TILES.