Permit: T01CM00979

Parcel: 13314227B


Addresses:

1400 N WILMOT RD

Inspection Status: Partial Approval

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
01/28/2002 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection 0000*INSPECTED OPENINGS FOR FIRE DAMPERS OK TO PROCEED.
01/28/2002 MECHANICAL - INTERMEDIATE Approved
10/05/2001 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection 0000*INSPECTION ON FIRE DAMPERS THRU THE ROOF OK TO COMPLETE INSTALLATION.
09/21/2001 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection 0000*INSPECTION ON FIRE DAMPERS THRU SIDE WALK OK TO COMPLETE W/ANGLE IRON.
09/18/2001 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection 0000*INSPECTION ON HIGH PRESSURE DUCT PHASE I OK TO INSULATE DUCT. CUT SHEATHLING BAK ON OPENINGS THRU ROOF FOR FIRE DAMPERS. SHEET ROCK ALL THE WAY UP NEED TO CONFIRM MIN 1/4" CLEARANCE ON FIRE DAMPERS PROVIDE DETAIL FOR FIRE DAMPERS THRU ROOF PENETRATION.