Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T01CM00979
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/02/2002 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
11/14/2001 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*OK TEMP C OF O PHASE ONE. | |
11/13/2001 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000* | |
11/07/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245*NOTES 1.) BOND BUSHINGS IN 480V PANELS NEED BONDING JUMPER INSTALLED 2.) PROVIDE COPY OF LETTER APPROVING EM. POWER SYSTEM OPERATION PRIOR TO OCCUPANCY, BY AGENCY CONDUCTING TEST. |