Permit: T01CM00970

Parcel: 108213260

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T01CM00970

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/31/2001 MECHANICAL - FINAL Approved IVRS - Inspection 0000*ALL CORRECTIONS HAVE BEEN MADE.
05/30/2001 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*RE-ROUTE CONDENSATE AWAY FROM ACCESS TO FAN COIL #3.
05/18/2001 MECHANICAL - FINAL Partial Approval FAN COIL #3.BRACE ON LEFT END NEEDS TO BE SPREAD TOWARD LEFT END OF UNIT.RE ROUTE CONDENSATE AWAY FROM CENTER SECTION AS NECESSARY.
05/14/2001 MECHANICAL - FINAL Denied IVRS - Inspection 0999* THIS JOB IS STILL REJECTED. FRONT OF FAN COILS ARE BLOCKED BY UNI STRUT SUPPORTS CONDENSATE PIPING AND REFRID. LINE PIPING THIS WAS BROUGHT TO MMI'S ATTEN. ON 4-27-01