Permit: T01CM00918

Parcel: 125041690


Addresses:

2331 E 2ND ST

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
12/04/2002 BUILDING - FINAL Approved IVRS - Inspection 0000*
12/02/2002 BUILDING - FINAL Denied IVRS - Inspection 0999*/ 1) HANDRAIL GETS PROGRESSIVELY HIGHER TO TOP OF STAIRS. IRC REQUIRES ONE HEIGHT BETWEEN 34 AND 38" 2) PROVIDE STEP LADDER TO ACCESS ATTIC (UNABLE TO CHECK #6 ABOVE)
10/28/2002 BUILDING - FINAL Denied IVRS - Inspection 0999*/ 1) A/C CONDENSATE DRAIN NOT CONNECTION 2) GAS BOND BROKEN 3) FILL OPEN K.O. IN PANEL 4) SUPPORT FURNACE WATER HEATER VENT 5) HAND RAIL TO HIG AND TO SHORT AND MUST RETURN TO WALL 6) FURNACE REQUIRES SPARK SHEILD. VERTICAL CONNECTION AND 30" MAINTENANCE PLATFORM 7) RE-GRADE EXISTING HOUSE 8) FRONT UNIT OK