Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/09/2001 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000* | |
| 05/08/2001 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0999* 1) BANG PLATES NEEDED OVER SUB PANELS 2) WIRING TO LAU. EXHAUST FAN MISSING 3) ROUTE ROMEX INTO BOXES AT DEMISING WALL 4) ADD BLOCKS TO SUPPORT PANEL FEEDER CABLE 5) HALL SMOKE DETECTORS NOT IN 6) RELOCATE SMOKE DETECTORS IN HALL CLOSER TO BEDROOMS 36" AWAY FROM RETURN AIR DUCT |