Permit: T01CM00913

Parcel: 134083000


Addresses:

1145 S LUSK DR #01

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
06/08/2001 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
05/30/2001 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*1)FRONT UNIT-EXHAUST FAN WIRE NOT TERMINATED INTO CAN.2)SMOKE DETECTOR MUST BE 36" DISTANT FROM SUPPLY-OR-RETURN AIR REGISTER.3)REMOVE SLACK AND SECURE ROMEX INTO 2 BATH EXHAUST FAN.4)LABEL PANEL.USE DYMO TAPE-ALUM.-SCREW TO METAL CAN.NO "MAGIC MARKER".
REAR UNIT.1)EXHAUST FAN WIRING NOT TERMINATED.2)STRAIGHTEN OUT CABLE RUNS AT ENDS AND SECURE WITH STAPLES.EXCESSIVE SLACK MAY END UP BETWEEN DRYWALL AND FRAME WORK NAILED OR PINCHED.