Permit: T01CM00887

Parcel: 119180890


Addresses:

3672 S 16TH AV


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T01CM00887

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/04/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
05/29/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999*160 AMP FUSES NOT INSTALLED.RECALL AND HAVE PLANS.A REFEE IS DUE BEFORE THE NEXT INSPECTION.
05/14/2001 ELECTRIC - FINAL Partial Approval 1) PLEASE MAKE DISCONNECTS ON ROOF MORE STOUT 2) NEED CALCULATIONS AND FINAL APPROVED RESULTS FOR THE 200 AMP FEEDER(*SUB PANEL) DERATING FACTOR. MUST BE STAMPED BY AN ARCHITECT OR ENGINEER (ELECTRICAL)
05/10/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999* NOTE: ENGINEER TO SHOW FIGURES FOR ROOF TOP PANEL FEEDER (FOR 114 DEGREES - 122 DEGREES F) AND APPROVE FIND FIGURE FOR THIS OCCUPANCY
1) SERVICE NEEDS GROUNDING BUSHINGS AND BONDING JUMPER, 3 AREAS 2) BOND SERVICE DISCONNECT 3) LINE AND LOAD SIDE REVISED ON MAIN DISCONNECT 4) A/C UNIT DISCONNECT. CHECK FOR #6 COPPER AND #10 EQUIPMENT GROUND. USE BIGGER SUPPORT TO HOLD DISCONNECTS, NEED K.O. SEALS
05/08/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999* 1) LOOSE FITTINGS
2) SUPPORT CONDUIT AS PER CODE 3) NEED BONDING DEVICE AT SERVICE CONDUIT 4) SUPPORT JUNCTION BOXES ABOVE PANEL 5) SUPPORT M/C CABLE AS PER CODE EXHAUST FAN 6) NEED SUPPORT WIRES ON CEILING OUTLETS
7) EMERGENCY FLOOD NOT LOCATED AS PLAN AND MISSING ONE.
05/07/2001 ELECTRIC - FINAL Not ready for Inspection LOCKED INSP TO RESUME TOMARROW HAVE WALLS OPENED PER LAST REQUEST