Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T01CM00861


Addresses:

1354 W IRVINGTON RD


Inspection Status: Approved

Inspection History: ELECTRIC - TEMPORARY POLE

Permit Number - T01CM00861

Inspection Description - ELECTRIC - TEMPORARY POLE

Inspection Status - Approved

Date Description Inspector Results Comments
11/21/2001 ELECTRIC - TEMPORARY POLE Approved IVRS - Inspection 0000*
11/15/2001 ELECTRIC - TEMPORARY POLE Denied IVRS - Inspection 0999*A REFEE IS DUE BEFORE THE NEXT INSPECTION 1.)MUST CHANGE PERMIT TO REFLECT CURRENT GENERAL CONTRACTOR PLEASE ALSO SUBMIT LETTER OF THE LICENSED CONTRACTOR 2.) NEED LETTER ON THE ENGINEERS APPROVAL ON THE ALTERNATE METHOD OF GROUNDING USED IE. RODS. 3.) PLEASE HAVE FORMAL NOTATION OF PLAN...TYING IN UNIT NUMBERS WITH PANEL NUMBERS 4.) DISCONNECT 101 GREEN M.B.J. SCREW IS CROSS THREADES, CORRECT PER MIN CODE ALTERNATE METHODI. 5.) THE 2 X 8 FRAMING TO POUR CONCRETE APRON, 3 FT FRONT OF SERVICE WILL BE OK SUBJECT TO OTHER INSPECTORS GAIN HEIGHT FOR MIN CODE REQUIRMENT.6.) METER BASE WIRING INCOMPLETE. 7.) NEED COMPLETE SUPPLY SIDE BONDING OF SERVICE SIZE PER 250-102. 8.) BOND NEUTRALS TO CAN 9.) OTHER PROBLEMS.