Inspection Status: Approved
Inspection History: ELECTRIC - TEMPORARY POLE
| Date |
Description |
Inspector |
Results |
Comments |
| 11/21/2001 |
ELECTRIC - TEMPORARY POLE |
|
Approved |
IVRS - Inspection 0000* |
| 11/15/2001 |
ELECTRIC - TEMPORARY POLE |
|
Denied |
IVRS - Inspection 0999*A REFEE IS DUE BEFORE THE NEXT INSPECTION 1.)MUST CHANGE PERMIT TO REFLECT CURRENT GENERAL CONTRACTOR PLEASE ALSO SUBMIT LETTER OF THE LICENSED CONTRACTOR 2.) NEED LETTER ON THE ENGINEERS APPROVAL ON THE ALTERNATE METHOD OF GROUNDING USED IE. RODS. 3.) PLEASE HAVE FORMAL NOTATION OF PLAN...TYING IN UNIT NUMBERS WITH PANEL NUMBERS 4.) DISCONNECT 101 GREEN M.B.J. SCREW IS CROSS THREADES, CORRECT PER MIN CODE ALTERNATE METHODI. 5.) THE 2 X 8 FRAMING TO POUR CONCRETE APRON, 3 FT FRONT OF SERVICE WILL BE OK SUBJECT TO OTHER INSPECTORS GAIN HEIGHT FOR MIN CODE REQUIRMENT.6.) METER BASE WIRING INCOMPLETE. 7.) NEED COMPLETE SUPPLY SIDE BONDING OF SERVICE SIZE PER 250-102. 8.) BOND NEUTRALS TO CAN 9.) OTHER PROBLEMS. |