Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - UNDERGROUND
Permit Number - T01CM00861
Inspection Description - ELECTRIC - UNDERGROUND
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/07/2001 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection 0999*1.) SERVICES TO BONDED 250-58 2.) GROUNDING ELECTRODES TO BE CONNECTED TO GROUNDED CONDUCTORS 250-24. 3.) BOND DEVICES NEEDED ON ALL RACE WAYS AT SERVICE 250-94.4.) BONDING OF DEVICES TO BE AS PER CODE 250-102. 5.) DOUBLE LUGING AT TERM CAN 6.) MAXIMUM HIGHTH OF DISCONNECT 6'7" 7.) LABELS SERVICES & DISCONNECTS. 8.) PLEASE HAVE ALL BOXES OPENED FOR FULL INSPECTIONS. | |
11/05/2001 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection 0000*SERVICE #1 HAS NO GROUNDING ELECTRODE SYSTEM PLEASE SHOW ALTERNATE METHOD OF GROUNDING ON APPROVED PLANS UGER MISSED. SERVICE 2 PLEASE CHANGE PLANS, UFER MISSED NEED APPROVED GROUNDING METHOD CONNECTIONS TO DOD INCORRECTED UNDERGROUND SERVICE CONDUITS APPROVED. | |
10/10/2001 | ELECTRIC - UNDERGROUND | Denied | LOCKED PLEASE RECALL. | |
03/27/2001 | ELECTRIC - UNDERGROUND | Partial Approval | APPROVED: 1) SUB PANEL FEEDER CONDUITS 6 1 1/2" PVC 2) SECONDARY CONDUITS 2 4" PVC TO SERVICE ENTRANCE #1. DENIED: SERVICE #2 INCOMPLETE NEED 2 4" CONDUITS AND MUST ALL BE PER CURRENT PLAN OR CITY APPROVED REVISION |