Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - TEMP POWER FOR TEST
Permit Number - T01CM00843
Inspection Description - ELECTRIC - TEMP POWER FOR TEST
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/04/2002 | ELECTRIC - TEMP POWER FOR TEST | Approved | IVRS - Inspection 0000*PLEASE CLEAR TEMP POWER FUEL & TEST. OK. TO CLEAR TEMP POWER FOR FUEL & TESTING. OK TO ENERGIZE. RTU 1/TRU-2 | |
12/31/2001 | ELECTRIC - TEMP POWER FOR TEST | Partial Approval | GROUNDING BUSHING AND BONDING JUMPER REQUIRED AT ALL NIPPLE FOR SERVICE ENTRANCE RACEWAY BONDING WILL NEED APPROVED REVISION TO MDP. CHANGE IN WIRE SIZE AND BREAKER RATINGS. | |
12/29/2001 | ELECTRIC - TEMP POWER FOR TEST | Not ready for Inspection | IVRS - Inspection 0000*JERRY, I TOLD DAV HEAD (ARC), THAT BOND BUSHINGS OR BOND LOCKNUTS ARE REQUIRED IN THE C.T. CAN BECAUSE THE SECONDARY ARE ALREADY MADE UP, I DIDNT WRITE IT DOWN OR CALL IT BECAUSE HE SAID YOU ALREADY LOOKED AT IT AND DIDNT SAY TO. I TOLD HIM THAT WE AS INSPECTORS ARE CALLING THEM ALL THAT WAY OR REQUIEING BONDING PER 250-96 NEC' 99 I WILL LET YOU MAKE THE CALL. HE'S CALLING IT BACK IN FOR MONDAY 12/31/01. THE GEAR WAS NOT COMPLETER ON THE MAKE-UP. | |
12/28/2001 | ELECTRIC - TEMP POWER FOR TEST | Not ready for Inspection | IVRS - Inspection 0000* |