Permit: T01CM00842

Parcel: 141130120


Addresses:

9050 E VALENCIA RD


Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T01CM00842

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
03/21/2001 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection 0000* ADD SUPPORTS TO MC CABLE MUST BE SUPPORTED WITHIN 12" OF BOX. WIRES USED FOR SUPPORT MUST BE ATTACHED TO WOOD TRUSSES AND TO GRID TO PREVENT SWINGING. DO NOT USE GRID SYSTEM SUPPORT WIRES - INSTALL YOUR OWN. TIE TOP AND BOTTOM. LEAVE A FEW TILES OPEN FOR FINAL INSP.
03/20/2001 ELECTRIC - ABOVE CEILING Not ready for Inspection