Permit: T01CM00832

Parcel: 13329010A

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
08/01/2002 MECHANICAL - FINAL Approved IVRS - Inspection 0000*OK FOR C OF O.
07/31/2002 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*1.) YOU CANNOT REDUCE THE SIZE OF A GAS LINE 1/2" THEN INCREASE BACK TO 3/4" USE 3/4" THE ENTIRE LENGTH. 2.) SILICONE IS NOT GOING TO FIX A CROSSTHREADED FITTING. THREAD FITTING ON CONDENSATE DRAIN CORRECTLY INTO OUTLET ON UNIT.
07/30/2002 MECHANICAL - FINAL Denied IVRS - Inspection 0999*1.) PROVIDE AN OUTSIDE AIR VENT ON AC UNIT AS PER SECTION 403.3 2000 IMC. 2.) 3/8 I.D. GAS FLEX CONNECTOR NOT ADEQUATE SIZE FOR 135,000 BTU. SEE LISTING ON FLEX CONNECTOR. 3.) THREADED FITTING ON CONDENSATE DRIAN LINE THREADED INTO UNIT. 4.) SECURE ELEC. DISCONNECT. 5.) #8 WIRE FROM ELEC. DISCONNECT TO AC UNIT NOT ADEQUATE FOR 60 AMP CIRCUIT. 6.) PROVIDE A ROOF JACK WHERE LOW VOTTAGE CONDUIT PENETRATES ROOF. RECALL FOR FINAL INSPECTION.