Permit: T01CM00832

Parcel: 13329010A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/06/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*OK C OF O.
08/02/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*SERVICE DISCONNECT OK, FUSES WIRING OK GROUNDING PARTIALLY OK 99 NEC 250-104 THE WATER BOND HAS TO GO TO 1.) SERVICE DISCON ENCLOSURE. 2.) GROUNDING ELECTRODE CONDUCTOR 3.) GAS LINE 4.) GROUND RODS OR UFER.
07/30/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0245*NOTES ITEMS 1 & 2 OR PER MAC C. 1.) NEW SERVICE INSTALLED PER REVISED PLAN 3-27-02. DISC SW. TO CLOSE TO METER ENCLOSURE, CANNOT BY PASS MECHANISM TO OPEN DOOR OF DISC. WHILE SWITCHED ON , NEED TO CHECK FUSES & WIRING. 2.) NEED VERIFICATION APPROVAL AS CALLED OUT BY PLAN FOR, WATER PIPE BONDING, (2) GROUND RODS, NEUTRAL BONDING. 3.) EXPOSED SPLICES FOR PUMP UNDER COUNTER MUST BE IN APPROVED J-BOX. 4.) PLANS CALL FOR 20 AMP RECEPTS, AND SWITCHES.
07/03/2002 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*OK TO CLEAR.