Permit: T01CM00811

Parcel: 125081000


Addresses:

2419 E BROADWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T01CM00811

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
07/27/2001 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection 0000*
07/12/2001 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0245*NOTE 1.) SUPPORT MC CABLE WITHING 12" EACH BOX OR FIXTURE IF OVER 6" IN LENGTH. ART 334-10 N.E.C. 2.) 1 SIEZMIC WIRE REQUIRED ON CAN LTS. 300-11 N.E.C. #9287 CITY ORDIN.