Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T01CM00778

Parcel: 110046100

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T01CM00778

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
05/15/2001 FRAMING Approved IVRS - Inspection 0000*
05/14/2001 FRAMING Denied IVRS - Inspection 0999*/ 1) ITEMS 2, 3, 5 AND 11 FROM 5/11/01 NOT COMPLIED WITH
05/11/2001 FRAMING Denied 1) BOND GAS LINE 2) STAIR STRINGERS NOT PROPERLY SUPPORTED-SCE 4/SD3 3) FIRE/DRAFT STOP STAIRS 4) HEADERS FOR 2030 WINDOWS MUST BEAR ON TRIMMERS SHIM ALL TRIMMERS 5) ELECTRIC OUTLETS AND WIRE NOT ALLOWED IN RETURN AIR 6) MASTER BEDROOM 5040 WINDOW WALL NOT NAILED AT PLATE 7) MASTER BEDROOM TUB LEAK 8) BEARING STUD BY STAIR AND LAV 2ND FLOOR-REQUIRES ADDED STUD 9) F/B LOFT/ENTRY CEILING SOUTH WALL 10) WATER HEATER VALVE LEAK 11) LAUNDRY #2 S/W FURRING NAIL AT 4" ON CENTER AND PROVIDE TOP BLOCK 12) WIRE BELOW CEILINGS 13) KITCHEN GAS/ELECTRIC BOXES NOT SECURE