Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T01CM00759
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/23/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
07/20/2001 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*1.) PNL NEEDS A 200A MAIN CB OR IF OK TO FEED FROM PNL A NEED TO USE 22,000 AIC RATED 200A CB 2.) PLANS DO NOT SHOW WHATS BEEN INSTALLED MISSING FEED THUR PANEL A-NO 400A MAIN CB, MISSING 200A MAIN LB ON PNLB 3.) STRAP FLEX UNDER COUNTER 4.) ROOF OK PLEASE GET AN APPROVAL ON PLAN CHANGE ON ITEMS #2 | |
07/20/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*APPROVED CHANGES FROM ORIGINAL PLAN NOT ON SITE YET. 11:15 AM |