Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/23/2001 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 07/20/2001 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*1.) PNL NEEDS A 200A MAIN CB OR IF OK TO FEED FROM PNL A NEED TO USE 22,000 AIC RATED 200A CB 2.) PLANS DO NOT SHOW WHATS BEEN INSTALLED MISSING FEED THUR PANEL A-NO 400A MAIN CB, MISSING 200A MAIN LB ON PNLB 3.) STRAP FLEX UNDER COUNTER 4.) ROOF OK PLEASE GET AN APPROVAL ON PLAN CHANGE ON ITEMS #2 |
| 07/20/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*APPROVED CHANGES FROM ORIGINAL PLAN NOT ON SITE YET. 11:15 AM |