Permit: T01CM00759

Parcel: 11008305F


Addresses:

2485 N SWAN RD #101


Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T01CM00759

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
07/13/2001 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection 0000*
07/09/2001 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0245*1.) DO NOT SUPPORT RACEWAYS TO RACEWAY 300-11 B 2.) SUPPORT MC CABLE WITHIN 12" EACH BOX OR TERMINATION, AND AT 6" INTERVALS, 6" FIXTURE WHIPS EXCEPTED (EXEMPT.) 3.) SUPPORT EMT CONDUIT WITHIN 3" EACH BOX AND 10' INTERVALS. 334-10 AND 348-13 N.E.C. 4.) WHEN SUPPORTING WITH CEILING WIRE, MUST BE TIED OFF BOTH ENDS CONDUIT OR BOXES APT 300-11
06/29/2001 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*OK TO CLEAR TEMP POWER BOND POSTED, FOR TESTING OF EQUIPMENT.
06/28/2001 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection 0000*1.) CONTRACTOR ALSO WANTS TEMP POWER FOR TESTING EQUIP. BOND POSTED. 2.) PRIOR TO RELEASE FOR TEMP INSTALL GFCR RECEPTS FOR CONST TOOLS.
06/26/2001 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection 0000*CALL FOR TEMP POWER 1.) INSTALL FUSES, RETECTION CLIPS 2.) INSTALL PROPER ADDRESS LABEL.