Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 07/13/2001 |
ELECTRIC - ABOVE CEILING |
|
Approved |
IVRS - Inspection 0000* |
| 07/09/2001 |
ELECTRIC - ABOVE CEILING |
|
Denied |
IVRS - Inspection 0245*1.) DO NOT SUPPORT RACEWAYS TO RACEWAY 300-11 B 2.) SUPPORT MC CABLE WITHIN 12" EACH BOX OR TERMINATION, AND AT 6" INTERVALS, 6" FIXTURE WHIPS EXCEPTED (EXEMPT.) 3.) SUPPORT EMT CONDUIT WITHIN 3" EACH BOX AND 10' INTERVALS. 334-10 AND 348-13 N.E.C. 4.) WHEN SUPPORTING WITH CEILING WIRE, MUST BE TIED OFF BOTH ENDS CONDUIT OR BOXES APT 300-11 |
| 06/29/2001 |
ELECTRIC - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*OK TO CLEAR TEMP POWER BOND POSTED, FOR TESTING OF EQUIPMENT. |
| 06/28/2001 |
ELECTRIC - ABOVE CEILING |
|
Not ready for Inspection |
IVRS - Inspection 0000*1.) CONTRACTOR ALSO WANTS TEMP POWER FOR TESTING EQUIP. BOND POSTED. 2.) PRIOR TO RELEASE FOR TEMP INSTALL GFCR RECEPTS FOR CONST TOOLS. |
| 06/26/2001 |
ELECTRIC - ABOVE CEILING |
|
Not ready for Inspection |
IVRS - Inspection 0000*CALL FOR TEMP POWER 1.) INSTALL FUSES, RETECTION CLIPS 2.) INSTALL PROPER ADDRESS LABEL. |