Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T01CM00759
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/13/2001 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection 0000* | |
07/09/2001 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection 0245*1.) DO NOT SUPPORT RACEWAYS TO RACEWAY 300-11 B 2.) SUPPORT MC CABLE WITHIN 12" EACH BOX OR TERMINATION, AND AT 6" INTERVALS, 6" FIXTURE WHIPS EXCEPTED (EXEMPT.) 3.) SUPPORT EMT CONDUIT WITHIN 3" EACH BOX AND 10' INTERVALS. 334-10 AND 348-13 N.E.C. 4.) WHEN SUPPORTING WITH CEILING WIRE, MUST BE TIED OFF BOTH ENDS CONDUIT OR BOXES APT 300-11 | |
06/29/2001 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*OK TO CLEAR TEMP POWER BOND POSTED, FOR TESTING OF EQUIPMENT. | |
06/28/2001 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection 0000*1.) CONTRACTOR ALSO WANTS TEMP POWER FOR TESTING EQUIP. BOND POSTED. 2.) PRIOR TO RELEASE FOR TEMP INSTALL GFCR RECEPTS FOR CONST TOOLS. | |
06/26/2001 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection 0000*CALL FOR TEMP POWER 1.) INSTALL FUSES, RETECTION CLIPS 2.) INSTALL PROPER ADDRESS LABEL. |