Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 10/02/2001 |
PLUMBING - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* |
| 04/03/2001 |
PLUMBING - INTERMEDIATE |
|
Not ready for Inspection |
IVRS - Inspection 0000*/1. NEED 3/4" GAS LINE TO FURNACE, DON'T RUN. 2. GAS LINE THRU RETURN PLENIUM INSTALL SO YOU CAN REMOVE FURNACE, WITHOUT DISCONNECTING PIPE. 3. 6" CLR TO FURN. FLUE WITH WIRS BO PLASTIC H20 LINE, USE A B-VENT DBL JACKET TO REDUCE CLR. TO 1" COMBUSTIBLE, MOVE POLY H20 LINE AWAY FROM FURN. FLUE, INSTALL FIRE BLOCKS. |