Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/09/2001 |
BUILDING - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 07/05/2001 |
BUILDING - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) INSTALL POST TENSION TAG ON WATER SERVICE 2) LABEL ELECTRIC PANEL NOT A WATER BONDED SYSTEM 3) CUT SEWER CLEANOUTS TO GRADE 4) MAINTAIN MINIMUM EGRESS REQUIREMENT IN BEDROOM |
| 06/29/2001 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) LINE AND LOAD REVERSED AT GFCI KITCHEN LEFT OF RANGE 2) LABEL ELECTRIC PANEL FOR NO WATER BOND |