Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T01CM00708
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/22/2001 | ELECTRIC - ABOVE CEILING | Approved | ||
| 05/10/2001 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection 0999* 1) ATTACH FIXTURES TO GRID 2) SUPPORT MC CABLE AS PER CODE WITHIN 12" 334-10 (CANS) 3) FINISH SUPPORT WIRE TO TRAC 4) FILL ALL UNUSED OPENINGS 5) SUPPORT ALL BOXES WITH SUPPORT WIRES AND RIDIGIDLY SUPPORT FAN BOX 6) SUPPORT DATA STEREO AS PER CODE CNA NOT LAY ON GRID OR BE ATTACHED TO CEILING WIRES |