Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 05/11/2001 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* ABOVE CEILING OK EXCEPT FRONT AREA LEAVE 1 TILE OFF TO VIEW SUPPORT FOR TRACK LIGHTING AND FAN BOX, ALSO HAVE LADDER ON SITE |
| 04/23/2001 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000* |
| 04/20/2001 |
ELECTRIC - INTERMEDIATE |
|
Not ready for Inspection |
IVRS - Inspection 0000* 1) SUPPORT CONDUIT WITHIN 3' EACH BOX, PER NEC 348-13 2) USE BOX OFFSETS WHEN SUPPOTING CONDUIT TO METAL STUDS OR OTHER MEANS OTHER THAN FORCING EMT OVER TO STUD WITH 1 HOLE STRAPS 110-12 NEC 3) INSTALL GROUND PIGTAILS OR #10/32 SCREWS TO BOXES FOR DEVICES NEC 370-4 AND 250 4) OK TO COVER |