Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T01CM00708
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/11/2001 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000* ABOVE CEILING OK EXCEPT FRONT AREA LEAVE 1 TILE OFF TO VIEW SUPPORT FOR TRACK LIGHTING AND FAN BOX, ALSO HAVE LADDER ON SITE | |
| 04/23/2001 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* | |
| 04/20/2001 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000* 1) SUPPORT CONDUIT WITHIN 3' EACH BOX, PER NEC 348-13 2) USE BOX OFFSETS WHEN SUPPOTING CONDUIT TO METAL STUDS OR OTHER MEANS OTHER THAN FORCING EMT OVER TO STUD WITH 1 HOLE STRAPS 110-12 NEC 3) INSTALL GROUND PIGTAILS OR #10/32 SCREWS TO BOXES FOR DEVICES NEC 370-4 AND 250 4) OK TO COVER |